FIX Documentation is wrong #55

This commit is contained in:
Jean-Marc Collin
2023-02-24 08:06:29 +01:00
parent 46278ca9a3
commit 718315c4fe
2 changed files with 4 additions and 4 deletions

View File

@@ -309,8 +309,8 @@ The percentage is calculated with this formula:
Defaults values for coef_int and coef_ext are respectively: ``0.6`` and ``0.01``. Those defaults values are suitable for a standard well isolated room.
To tune those coefficients keep in mind that:
1. **if target temperature is not reach** after stable situation, you have to augment the ``coef_ext`` (the ``on_percent`` is too high),
2. **if target temperature is exceeded** after stable situation, you have to decrease the ``coef_ext`` (the ``on_percent`` is too low),
1. **if target temperature is not reach** after stable situation, you have to augment the ``coef_ext`` (the ``on_percent`` is too low),
2. **if target temperature is exceeded** after stable situation, you have to decrease the ``coef_ext`` (the ``on_percent`` is too high),
3. **if reaching the target temperature is too slow**, you can increase the ``coef_int`` to give more power to the heater,
4. **if reaching the target temperature is too fast and some oscillations appears** around the target, you can decrease the ``coef_int`` to give less power to the heater