* Refactor Presence Feature * Add PresenceFeatureManager ok * Python 3.13 * Fix presence test * Refactor power feature * Add Motion manager. All tests ok * Tests ok. But tests are not complete * All tests Window Feature Manager ok. * All windows tests ok * Fix all testus with feature_window_manager ok * Add test_auto_start_stop feature manager. All tests ok * Add safety feature_safety_manager Rename config attribute from security_ to safety_ * Documentation and release * Add safety manager direct tests * Typo --------- Co-authored-by: Jean-Marc Collin <jean-marc.collin-extern@renault.com>
This commit is contained in:
@@ -125,9 +125,9 @@ These parameters are sensitive and quite difficult to adjust. Please only use th
|
||||
|
||||
## Why is my Versatile Thermostat going into Safety Mode?
|
||||
|
||||
Safety mode is only available for VTherm types `over_switch` and `over_valve`. It occurs when one of the two thermometers (providing either the room temperature or the external temperature) has not sent a value for more than `security_delay_min` minutes, and the radiator had been heating at least `security_min_on_percent`. See [safety mode](feature-advanced.md#safety-mode)
|
||||
Safety mode is only available for VTherm types `over_switch` and `over_valve`. It occurs when one of the two thermometers (providing either the room temperature or the external temperature) has not sent a value for more than `safety_delay_min` minutes, and the radiator had been heating at least `safety_min_on_percent`. See [safety mode](feature-advanced.md#safety-mode)
|
||||
|
||||
Since the algorithm relies on temperature measurements, if they are no longer received by the VTherm, there is a risk of overheating and fire. To prevent this, when the above conditions are detected, heating is limited to the `security_default_on_percent` parameter. This value should therefore be reasonably low (10% is a good value). It helps avoid a fire while preventing the radiator from being completely turned off (risk of freezing).
|
||||
Since the algorithm relies on temperature measurements, if they are no longer received by the VTherm, there is a risk of overheating and fire. To prevent this, when the above conditions are detected, heating is limited to the `safety_default_on_percent` parameter. This value should therefore be reasonably low (10% is a good value). It helps avoid a fire while preventing the radiator from being completely turned off (risk of freezing).
|
||||
|
||||
All these parameters are configured on the last page of the VTherm configuration: "Advanced Settings".
|
||||
|
||||
@@ -151,14 +151,14 @@ last_temperature_datetime: "2023-12-06T18:43:28.346010+01:00"
|
||||
last_ext_temperature_datetime: "2023-12-06T13:04:35.164367+01:00"
|
||||
last_update_datetime: "2023-12-06T18:43:28.351103+01:00"
|
||||
...
|
||||
security_delay_min: 60
|
||||
safety_delay_min: 60
|
||||
```
|
||||
|
||||
We can see that:
|
||||
1. The VTherm is indeed in safety mode (`security_state: true`),
|
||||
2. The current time is 06/12/2023 at 18:43:28 (`last_update_datetime: "2023-12-06T18:43:28.351103+01:00"`),
|
||||
3. The last reception time of the room temperature is 06/12/2023 at 18:43:28 (`last_temperature_datetime: "2023-12-06T18:43:28.346010+01:00"`), so it's recent,
|
||||
4. The last reception time of the external temperature is 06/12/2023 at 13:04:35 (`last_ext_temperature_datetime: "2023-12-06T13:04:35.164367+01:00"`). The external temperature is over 5 hours late, which triggered the safety mode, as the threshold is set to 60 minutes (`security_delay_min: 60`).
|
||||
4. The last reception time of the external temperature is 06/12/2023 at 13:04:35 (`last_ext_temperature_datetime: "2023-12-06T13:04:35.164367+01:00"`). The external temperature is over 5 hours late, which triggered the safety mode, as the threshold is set to 60 minutes (`safety_delay_min: 60`).
|
||||
|
||||
### How to Be Notified When This Happens?
|
||||
The VTherm sends an event as soon as this happens and again at the end of the safety alert. You can capture these events in an automation and send a notification, blink a light, trigger a siren, etc. It's up to you.
|
||||
@@ -168,8 +168,8 @@ For handling events generated by VTherm, see [Events](#events).
|
||||
### How to Fix It?
|
||||
It depends on the cause of the problem:
|
||||
1. If a sensor is faulty, it should be repaired (replace batteries, change it, check the weather integration that provides the external temperature, etc.),
|
||||
2. If the `security_delay_min` parameter is too small, it may generate many false alerts. A correct value is around 60 minutes, especially if you have battery-powered temperature sensors. See [my settings](tuning-examples.md#battery-powered-temperature-sensor),
|
||||
3. Some temperature sensors don't send measurements if the temperature hasn't changed. So if the temperature stays very stable for a long time, safety mode can trigger. This is not a big issue since it will deactivate once the VTherm receives a new temperature. On some thermometers (e.g., TuYA or Zigbee), you can force a max delay between two measurements. The max delay should be set to a value lower than `security_delay_min`,
|
||||
2. If the `safety_delay_min` parameter is too small, it may generate many false alerts. A correct value is around 60 minutes, especially if you have battery-powered temperature sensors. See [my settings](tuning-examples.md#battery-powered-temperature-sensor),
|
||||
3. Some temperature sensors don't send measurements if the temperature hasn't changed. So if the temperature stays very stable for a long time, safety mode can trigger. This is not a big issue since it will deactivate once the VTherm receives a new temperature. On some thermometers (e.g., TuYA or Zigbee), you can force a max delay between two measurements. The max delay should be set to a value lower than `safety_delay_min`,
|
||||
4. As soon as the temperature is received again, safety mode will turn off, and the previous preset, target temperature, and mode values will be restored.
|
||||
5. If the external temperature sensor is faulty, you can disable safety mode triggering as it has a minimal impact on the results. To do so, see [here](feature-advanced.md#safety-mode).
|
||||
|
||||
|
||||