FIX security mode when hvac_off
This commit is contained in:
@@ -1697,6 +1697,8 @@ class VersatileThermostat(ClimateEntity, RestoreEntity):
|
|||||||
now - self._last_ext_temperature_mesure
|
now - self._last_ext_temperature_mesure
|
||||||
).total_seconds() / 60.0
|
).total_seconds() / 60.0
|
||||||
|
|
||||||
|
mode_cond = self._hvac_mode != HVACMode.OFF
|
||||||
|
|
||||||
temp_cond: bool = (
|
temp_cond: bool = (
|
||||||
delta_temp > self._security_delay_min
|
delta_temp > self._security_delay_min
|
||||||
or delta_ext_temp > self._security_delay_min
|
or delta_ext_temp > self._security_delay_min
|
||||||
@@ -1713,7 +1715,7 @@ class VersatileThermostat(ClimateEntity, RestoreEntity):
|
|||||||
)
|
)
|
||||||
|
|
||||||
ret = False
|
ret = False
|
||||||
if temp_cond and climate_cond:
|
if mode_cond and temp_cond and climate_cond:
|
||||||
if not self._security_state:
|
if not self._security_state:
|
||||||
_LOGGER.warning(
|
_LOGGER.warning(
|
||||||
"%s - No temperature received for more than %.1f minutes (dt=%.1f, dext=%.1f) and underlying climate is %s. Set it into security mode",
|
"%s - No temperature received for more than %.1f minutes (dt=%.1f, dext=%.1f) and underlying climate is %s. Set it into security mode",
|
||||||
@@ -1726,16 +1728,17 @@ class VersatileThermostat(ClimateEntity, RestoreEntity):
|
|||||||
ret = True
|
ret = True
|
||||||
|
|
||||||
_LOGGER.debug(
|
_LOGGER.debug(
|
||||||
"%s - checking security delta_temp=%.1f delta_ext_temp=%.1f temp_cond=%s climate_cond=%s switch_cond=%s",
|
"%s - checking security delta_temp=%.1f delta_ext_temp=%.1f mod_cond=%s temp_cond=%s climate_cond=%s switch_cond=%s",
|
||||||
self,
|
self,
|
||||||
delta_temp,
|
delta_temp,
|
||||||
delta_ext_temp,
|
delta_ext_temp,
|
||||||
|
mode_cond,
|
||||||
temp_cond,
|
temp_cond,
|
||||||
climate_cond,
|
climate_cond,
|
||||||
switch_cond,
|
switch_cond,
|
||||||
)
|
)
|
||||||
|
|
||||||
if temp_cond and switch_cond:
|
if mode_cond and temp_cond and switch_cond:
|
||||||
if not self._security_state:
|
if not self._security_state:
|
||||||
_LOGGER.warning(
|
_LOGGER.warning(
|
||||||
"%s - No temperature received for more than %.1f minutes (dt=%.1f, dext=%.1f) and on_percent (%.2f) is over defined value (%.2f). Set it into security mode",
|
"%s - No temperature received for more than %.1f minutes (dt=%.1f, dext=%.1f) and on_percent (%.2f) is over defined value (%.2f). Set it into security mode",
|
||||||
@@ -1748,7 +1751,7 @@ class VersatileThermostat(ClimateEntity, RestoreEntity):
|
|||||||
)
|
)
|
||||||
ret = True
|
ret = True
|
||||||
|
|
||||||
if not self._security_state and temp_cond:
|
if mode_cond and temp_cond and not self._security_state:
|
||||||
self.send_event(
|
self.send_event(
|
||||||
EventType.TEMPERATURE_EVENT,
|
EventType.TEMPERATURE_EVENT,
|
||||||
{
|
{
|
||||||
|
|||||||
Reference in New Issue